Purpose
To secure computer equipment on an access floor.
Note
Seek engineering assistance for the design of the tether spring. Typical equipment to tether:
- Disk drive controllers
- Disk drives
- High speed printers
- Magnetic tape drives
- Printer controllers
- Tape drive controllers
Recommendation
Provide horizontal motion isolators for computer equipment with the following characteristics:
Height
Height less than 1-1/2 times the base width.
Spacing
Moderate spacing (1-1/2 to 3') between equipment.
Cabinet
Flexible equipment cabinet that cannot be adequately strengthened or stiffened.
Internal Components
Internal components with HIGH vulnerability to vibrating motion.
Source: Noson, Perbix, SSD
Supplies Required
- Seismic level pads (with nylon boot)
- Floor penetration guard
- Steel cable tether (with springs)
- Eyebolt with expansion insert—1/2"diameter
- Machine bolt—1/2" diameter
Source: Noson, Perbix, SSD
Installation
- Provide a leveling pad below each corner of the equipment.
- Provide a penetration guard around access floor opening.
- Provide more slack in signal cables than in tether.
- Provide a steel tether between equipment and floor structure.